One of the most important criteria when purchasing an inverter
is its efficiency. The higher the efficiency, the lower the losses that are
incurred when converting direct current produced by the solar modules into alternating
current. SMA has set a new record for transformer-based units by achieving a
maximum efficiency of 95.6 %.
As well as ensuring the maximum effectiveness for the OptiCool® active cooling
system developed by SMA, an all-new, extra heavy duty extruded aluminium housing
with a double-chamber design also safely protects the electronic components
from the wind and weather.
Features:
- Easy plant design and reduced installation
costs
- SMA grid guard®
- Diagnosis and communication via Powerline Communication,
radio transmission or via data cable (RS232 or RS485)
- Extended temperature range –25 °C
to +60 °C
- For outdoor and indoor installation
- Connection on the AC- and DC-side with connectors
- Surge voltage protection with integrated thermally
monitored varistors
- With OptiCool® ventilation system –
suitable for outside installation
technical details
|
SB3300 |
details |
SB3300 |
details |
|
. |
. |
. |
. |
| Input |
. |
THD
of grid current |
< 4 % |
| Recc. maximum PV-power
(PPV) |
approx. 4300 WP |
|
for
PV-Plants in Germany |
Default
range of AC voltage (UAC) |
198
V – 260 V |
| Max. DC power (PDC, max) |
3800 W |
Possible range of AC voltage |
180 V – 265 V |
| Max. DC voltage (UDC, max) |
500 V |
AC frequency (fAC) |
49.8 Hz – 50.2
Hz |
| PV-voltage range, MPPT (UPV) |
200 V – 500 V |
Possible range of
AC frequency |
45.5 Hz – 54.5
Hz |
| Max. input current (IPV, max) |
20 A |
Short circuit proof |
yes, current control |
| DC voltage ripple (UPP) |
< 10 % |
Connection to utility |
AC Plug |
| Max. number of strings (parallel) |
3 |
Efficiency |
. |
| DC disconnection |
Snap cable connectors |
Max. Efficiency |
95.2 % |
| Thermally monitored varistors |
yes |
Euro-eta |
94.4 % |
| Ground fault monitoring |
yes |
Enclosure |
. |
| Pole confusion protection |
Short circuit diode |
accord. to DIN EN 60529 |
IP54 |
| Output |
. |
Mechanical Data |
. |
| Max. AC power (PAC, max) |
3600 W |
Width / height / depth in mm |
450 / 352 / 236 |
| Nominal AC power (PAC, nom) |
3300 W |
Weight |
approx . 38 kg |
| Data sheet |
|
|