The SB 1100 has an extended input voltage
range of up to 400 V DC. This allows the installation of very interesting module
configurations. The Sunnny Boy SB 1100 is designed for plants
with a DC power of up to 1350 Wp.
Features:
- Easy plant design and reduced installation
costs
- SMA grid guard integrated, anti-islanding unit
(MSD)
- Diagnosis and communication via Powerline Communication,
radio transmission or via data cable (RS232 or RS485)
- Extended temperature range 25 °C
to +60 °C
- Enclosure type IP65, suitable for outside installation
- Connection of DC input with waterproof snap
cable connectors
- Connection to AC utility with waterproof plug
- Surge voltage protection with integrated thermally
monitored varistors
Technical details
| SB1100. |
Details |
SB 1100 |
Details |
| . |
|
|
|
| Input |
|
THD of grid current |
<
4 % |
| Recc. maximum PV-power (PPV) |
approx.
1350 Wp |
Default range of AC voltage (UAC) |
198 - 260 V |
| Max. DC power (PDC, max) |
1210
W |
Possible range of AC voltage |
180 - 265 V |
| Max. DC voltage (UDC, max) |
400
V |
AC frequency (fAC) |
49,8 - 50,2 Hz |
| PV-voltage range, MPPT (UPV) |
139
V 400 V |
Possible range of AC frequency |
45,5 - 54,5 Hz |
| Max. input current (IPV, max) |
10
A |
Short circuit proof |
yes, current control |
| DC voltage ripple (UPP) |
<
10 % |
Connection to utility |
AC Plug |
| Max. number of strings (parallel) |
2 |
Efficiency |
|
| DC disconnection |
Snap
cable connectors |
Max. Efficiency |
93 % |
| Thermally monitored
varistors |
yes |
Euro-eta |
91,6
% |
| Ground fault monitoring |
yes |
Enclosure |
|
| Pole confusion protection |
Short
circuit diode |
accord. to DIN EN 60529 |
IP 65 |
| Output |
|
Mechanical Data |
|
| Max. AC power (PAC, max) |
1100
W |
Width / height / depth in mm |
322 / 320 / 180 |
| Nominal AC power (PAC, nom) |
1000
W |
Weight |
approx.. 21 kg |
| Data sheet |
|
|