Quattro 5kVA
Two AC inputs with integrated transfer switch
The Quattro can be connected to two independent AC sources, for example shore-side (grid-) power and a
generator, or two generators. The Quattro will automatically connect to the active source.
120/240 V input and output
The two AC inputs can be supplied from a split phase (up to 50 A per phase), dual AC (up to 50 A total), or single
phase AC (up to 50 A) source. The AC inputs can be connected to a different type of supply: one input may for
example be connected to a split phase source, and the other to a single phase source.
When an AC source is available, the Quattro will feed through the AC to its output. The output will therefore
mirror the AC input.
The inverter/charger connects to the neutral and the preferred input line (L1). Power needed to charge the
batteries will therefore be drawn from L1.
The Quattro switches to inverter operation when no AC source is available. The inverter output is 120 V single
phase. In Invert mode, the Quattro connects both output lines (L1 and L2) together to provide 120 VAC to loads
on either line. Any 240 VAC loads will therefore be supplied only when the Quattro is supplied by a split phase
AC source. This prevents heavy loads such as water heaters or 240 V air conditioners from discharging the
battery.
The Quattro provides seamless transfer (no-break functionality) on output L1. Output L2 connects to the inverter
after a short delay.
PowerControl - Dealing with limited generator, shore-side or grid power
The Quattro is a very powerful battery charger. It will therefore draw a lot of current from the generator or shore
side supply (34 A per Quattro at 120 VAC). A current limit can be set for L1 on both AC inputs. The Quattro will
then take account of other AC loads and use whatever is spare for charging, thus preventing the generator or
shore supply from being overloaded.
PowerAssist - Boosting shore or generator power
This feature takes the principle of PowerControl to a further dimension allowing the Quattro to supplement the
capacity of the alternative source. Where peak power is so often required only for a limited period, the Quattro
will make sure that insufficient shore or generator power is immediately compensated for by power from the
battery (L1 inputs only). When the load reduces, the spare power is used to recharge the battery.
Virtually unlimited power thanks to parallel operation
Up to 6 Quattro’s can operate in parallel. Six units 24/5000/120, for example, will provide 25kW / 30kVA output
power and 720 Amps charging capacity.
Three phase and split phase capability
Three resp. two units can be configured for three-phase resp. split phase output. But that’s not all: up to 6 units
can be paralleled per phase (max 18 units in a three phase system and max. 12 units in a split phase system).
Solar energy: AC power available even during a grid failure
The Quattro can be used both in off grid as well as grid connected PV and other alternative energy systems.
A grid connected PV system will shut down when the grid fails! Not anymore with a Quattro and batteries
A PV or other grid connected alternative energy system is a big investment. But it is incomplete: it will shut down
in the event of a grid failure. A Quattro plus battery can solve this deficiency: the Quattro will replace the grid
when needed, keeping the alternative energy system ‘on line’. During a power outage the system continues to
function ‘on its own’, as a small autonomous grid. The Quattro will stabilise the ‘mini grid’ by taking power from it
to recharge the battery when power generation exceeds consumption, and by supplying additional power when
demand exceeds the supply from the alternate sources. In addition, the Quattro can be used to connect an AC
generator to the mini grid.
System configuring has never been easier
After installation, the Quattro is ready to go.
If settings have to changed, this can be done in a matter of minutes with a new DIP switch setting procedure.
Even parallel and 3-phase operation can be programmed with DIP switches: no computer needed!
Alternatively, VE.Net can be used instead of the DIP switches.
And sophisticated software (VE.Bus Quick Configure and VE.Bus System Configurator) is available to configure
several new, advanced, features.
|
| Specifications |
| Quattro(4) |
12/5000/200 |
|
24/5000/120 |
|
48/5000/70 |
| PowerControl / PowerAssist |
Yes |
|
Yes |
|
Yes |
| Integrated Transfer switch |
Yes |
|
Yes |
|
Yes |
| AC inputs (2x) |
Input voltage range: 187-265 VAC ; Input Frequency: 45 – 65 Hz ; Power factor: 1 |
| Maximum feed through current (A) |
30 |
|
30 |
|
30 |
| INVERTER |
| Input voltage range (V DC) |
9,5 – 17 |
|
19 – 33 |
|
38 – 66 |
| Output (pure sinewave) |
Output voltage: 230 VAC ± 2% ; Frequency: 50 Hz ± 0,1% |
| Cont. output power at 25 °C (VA) (3) |
5000 |
|
5000 |
|
5000 |
| Cont. output power at 25 °C (W) |
4000 |
|
4250 |
|
4250 |
| Cont. output power at 40 °C (W) |
3000 |
|
3350 |
|
3350 |
| Peak power (W) |
8000 |
|
10 000 |
|
10 000 |
| Maximum efficiency (%) |
92 |
|
94 |
|
95 |
| Zero-load power (W) |
25 |
|
30 |
|
30 |
| Load shedding output |
Maximum load: 10A ; Switches off when no external AC source available |
| CHARGER |
| Charge voltage 'absorption' (V DC) |
14,4 |
|
28,8 |
|
57,6 |
| Charge voltage 'float' (V DC) |
13,8 |
|
27,6 |
|
55,2 |
| Storage mode (V DC) |
13,2 |
|
26,4 |
|
52,8 |
| Charge current house battery (A) (4) |
200 |
|
120 |
|
70 |
| Charge current starter battery (A) |
4 |
| Battery temperature sensor |
Yes |
| GENERAL |
| Multi purpose relay (5) |
Yes |
|
Yes |
|
Yes |
| Protection (2) |
a - f |
| Common Characteristics |
Operating temp.: -20 to +50°C (fan assisted cooling) Humidity (non condensing) : max 95% |
| ENCLOSURE |
| Common Characteristics |
Material & Colour: aluminium (blue RAL 5012) ; Protection category: IP 21 |
| Battery-connection |
Four M8 bolts (2 plus and 2 minus connections) |
| 230 V AC-connection |
Screw clamp 13mm² (AWG 6) |
| Weight (kg) |
30 |
| Dimensions (hxwxd in mm) |
444 x 328 x 240 |
| STANDARDS |
| Safety |
EN 60335-1, EN 60335-2-29 |
| Emission / Immunity |
EN55014-1, EN 61000-3-2 / EN 55014-2, EN 61000-3-3 |
| Automotive Directive |
2004/104/EC |
|
- Can be adjusted to 50 Hz
- Protection
- Output short circuit
- Overload
- Battery voltage too high
- Battery voltage too low
- 120VAC on inverter output
- Input voltage ripple too high
- Suitable for parallel and 3-phase operation
- At 25 °C ambient
- Non linear load, crest factor 3:1
- Multipurpose relay which can be set for general
alarm, DC undervoltage or genset start signal function
|
UpgradeYou can upgrade the product by selecting the respective upgrade below. |
| Quattro: |
|
Bewertungen
Wuyts W. Unpacked the unit and put it in operation.Perfect performance .The software and adapter for the communication with the unit was not really required.
|