Phoenix Inverter 120V
SinusMax - Superior engineering
Developed for professional duty, the Phoenix range of inverters is suitable for the widest range of
applications. The design criteria have been to produce a true sine wave inverter with optimised efficiency
but without compromise in performance. Employing hybrid HF technology, the result is a top quality
product with compact dimensions, light in weight and capable of supplying power, problem-free, to any
load.
Extra start-up power
A unique feature of the SinusMax technology is very high start-up power. Conventional high frequency
technology does not offer such extreme performance. Phoenix inverters, however, are well suited to power
up difficult loads such as refrigeration compressors, electric motors and similar appliances.
Virtually unlimited power thanks to parallel, 3-phase and split phase operation capability
Up to 6 units Phoenix 24/3000 can operate in parallel to achieve higher power output. Six 24/3000 units,
for example, will provide 15 kW / 18 kVA output power. Operation in 3-phase, split phase and 2 leg three
phase configuration is also possible.
To transfer the load to another AC source: the automatic transfer switch
If an automatic transfer switch is required on models rated at 2500 VA or more, we recommend to use the
Phoenix Multi instead. The switch is included in these products and the charger function of the Multi can be
disabled. For our lower power models we recommend the use of our Filax Automatic Transfer Switch.
Computers and other electronic equipment will continue to operate without disruption because both the
Filax and the Phoenix Multi feature a very short switchover time (less than 16 milliseconds).
Computer interface
All models rated at 2500 VA or more have a RS-485 computer interface. All you need to connect to your
PC is our data link MK2 (see under accessories). This data link takes care of galvanic isolation between
the inverter and the computer, and converts from RS-485 to RS-232. Together with the VEConfigure
software, which can be downloaded free of charge from our website www.victronenergy.com, all
parameters of the inverters can be customised. This includes output voltage and frequency, over and
under voltage settings and programming the relay. This relay can for example be used to signal several
alarm conditions, or to start a generator.
The inverters can also be connected to VE.Net, the new power control network of Victron Energy, or to
other computerised monitoring and control systems.
New applications of high power inverters
The possibilities of paralleled high power inverters are truly amazing. For ideas, examples and battery
capacity calculations please refer to our book -Energy Unlimited- (available free of charge from Victron
Energy and downloadable from www.victronenergy.com).
|
| Specifications |
| Phoenix Inverter |
12 Volt |
12/180 |
12/350 |
12/750 |
C 12/1200 |
C 12/1600 |
C 12/2000 |
12/3000 (4) |
| 24 Volt |
24/180 |
24/350 |
24/750 |
C 24/1200 |
C 24/1600 |
C 24/2000 |
24/3000 (4) |
| 48 Volt |
48/180 |
48/350 |
48/750 |
|
|
|
48/3000 (4) |
| Input voltage range (V DC) |
10,5 - 15,5 |
10,5 - 15,5 |
10,5 - 15,5 |
9,5 - 16,0 |
9,5 - 16,0 |
9,5 - 16,0 |
9,5 - 16,0 |
| 21,0 - 31,0 |
21,0 - 31,0 |
21,0 - 31,0 |
19,5 - 32,2 |
19,5 - 33,0 |
19,5 - 33,0 |
19,5 - 33,0 |
| 42,0 - 62,0 |
42,0 - 62,0 |
42,0 - 62,0 |
|
|
|
38,0 - 66,0 |
| Cont. output power at 25 °C (VA) (5) |
180 |
350 |
750 |
1200 |
1600 |
2000 |
3000 |
| 180 |
350 |
750 |
1200 |
1600 |
2000 |
3000 |
| 180 |
350 |
750 |
|
|
|
3000 |
| Cont. power at 25 °C / 40 °C (W) |
175 / 150 |
300 / 250 |
700 / 650 |
1000 / 900 |
1300 / 1200 |
1600 / 1450 |
2500 / 2000 |
| 175 / 150 |
300 / 250 |
700 / 650 |
1000 / 900 |
1300 / 1200 |
1600 / 1450 |
2500 / 2000 |
| 175 / 150 |
300 / 250 |
700 / 650 |
|
|
|
2500 / 2000 |
| Peak power (W) |
200 |
500 |
1400 |
2200 |
2300 |
4000 |
6000 |
| 200 |
500 |
1400 |
2200 |
3000 |
4000 |
6000 |
| 200 |
500 |
1400 |
|
|
|
6000 |
| Max. efficiency 12 / 24 / 48 V (%) |
91 / 92 / 92 |
90 / 91/ 92 |
91 / 93 / 94 |
93 / 94 |
93 / 94 |
93 / 94 |
93 / 94 / 95 |
| Zero-load power 12 / 24 / 48 V (W) |
2,2 / 3,0 / 4,0 |
3,0 / 3,5 / 4,0 |
12 / 12 / 12 |
8 / 11 |
8 / 11 |
10 / 13 |
15 / 15 / 16 |
| Zero-load power in AES mode |
n. a. |
n. a. |
3 / 4 / 5 |
5 / 8 |
5 / 8 |
8 / 10 |
10 / 10 / 12 |
| Multi purpose relay driver or relay (6) |
|
|
|
relay driver (7) |
relay driver (7) |
relay driver (7) |
relay |
| Protection (3) |
a,b,d,h |
a,b,d,h |
a,b,d,h |
a,b,c,d,f,g,h |
a,b,c,d,f,g,h |
a,b,c,d,f,g,h |
a - h |
| Common Characteristics (2,3) |
Output: 230 V ± 2% / 50/60 Hz ± 0,2% (switch selectable) Operating temperature range: -20 to +50°C (fan assisted cooling) Humidity (non condensing) : max 95% |
| ENCLOSURE |
| Material & Colour |
aluminium (blue Ral 5012) |
| Battery-connection |
1) |
1) |
Screw conn. |
1) |
1) |
M8 studs |
M8 studs |
| 230 V AC-connection |
IEC-320 (IEC-320 plug included) or Schuko |
G-ST18i |
G-ST18i |
Spring-clamp |
Screw-clamp |
| Protection category |
IP 20 |
IP 20 |
IP 20 |
IP 21 |
IP 21 |
IP 21 |
IP 21 |
| Weight (kg) |
2,7 |
3,5 |
2,7 |
10 |
10 |
12 |
18 |
| Dimensions (hxwxd in mm) |
72x132x200 |
72x155x237 |
72x180x295 |
375x214x110 |
375x214x110 |
520x255x125 |
362x258x218 |
| ACCESSORIES |
| Remote panel (RS 485 port) |
|
|
|
Yes(PIV) |
Yes(PIV) |
Yes(PIV) |
Yes(PIV) |
| Remote on-off switch |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
Yes |
| Automatic transfer switch |
Filax |
Filax |
Filax |
Phoenix Multi |
Phoenix Multi |
Phoenix Multi |
Phoenix Multi |
| STANDARDS |
| Safety |
EN 60950 |
EN 60950 |
EN 60950 |
EN 60335-1 |
EN 60335-1 |
EN 60335-1 |
EN 60335-1 |
| Emission / Immunity |
EN55014-1 / EN 55014-2 |
| Automotive Directive |
|
|
|
95/54/EC und 2004/104/EC |
|
- Battery cables of 1.5 meter (12/180 with cigarette plug)
- 115 V AC on request
- Protection
- Output short circuit
- Overload
- Battery voltage too high
- Battery voltage too low
- Battery reverse polarity detection
- 230 V AC on inverter output
- Input voltage ripple too high
- Temperature too high
- Suitable for parallel and 3-phase operation
- Non linear load, crest factor 3:1
- Multipurpose relay which can be set for general alarm,
DC undervoltage or genset start signal function
- Relay driver: open collector 66V 40mA
|
UpgradeYou can upgrade the product by selecting the respective upgrade below. |
| Phoenix Inverter: |
|
|