BMV 600 - Precision Battery Monitoring
Precision monitoring
The essential function of a battery monitor is to calculate ampere-hours consumed and the state of charge of a battery. Ampere-hours consumed is calculated by integrating the current flowing in or out of the battery. In case of a constant current, this integration is equivalent to current multiplied by time. A discharge current of 10A during 2 hours, for example, amounts to 20Ah consumed. All our battery monitors are based on a powerful microprocessor, programmed with the algorithms needed for precision monitoring.
Standard information and alarms
- Battery voltage (V)
- Battery charge/discharge current (A)
- Ampere-hours consumed (Ah)
- State of charge (%)
- Time to go at the current rate of discharge
- Visual and audible alarm: over- and under voltage, and/or battery discharged
low cost ultra high resolution monitor
- Highest resolution: 10mA (0,01A) with 500A shunt.
- Lowest current consumption: 1mA.
- Easiest to wire: the BMV 601 comes with shunt, 10 meter RJ 12 UTP cable and 2 meter battery cable with fuse. No other components needed.
- Easiest to install: separate front bezel for square or round appearance; ring for rear mounting and screws for front mounting.
VE.Net Battery Controller: any number of batteries
- One VE.Net panel will connect to any number of battery controllers.
- Comes with 500A/50mV shunt and can be programmed for any other shunt.
- With use, abuse and data memory.
- Temperature sensor and connection kit included
| Technical Data |
| BMV 602 |
| Power supply voltage range |
9 - 95 VDC |
| Current draw (ohne Beleuchtung) |
1 mA |
| Input Voltagesbereich DC |
9 - 95 VDC |
| Battery capacity (Ah) |
20 - 9999 Ah |
| Operating temperature range |
-20°C +50°C (0°F - 120°F) |
| RESOLUTION (with 500 A shunt) |
| Current |
± 0,01 A |
| Voltage |
± 0,01 V |
| Amp hours |
± 0,1 Ah |
| State of charge (0 – 100 %) |
± 0,1 % |
| Time to go |
± 1 min |
| Temperature (0 - 50°C or 30 - 120°F) |
n. a. |
| Accuracy of current measurement |
± 0,3 % |
| Accuracy of voltage measurement |
± 0,4 % |
| Potential free contacts |
60V/1A (N/O) |
| INSTALLATION AND DIMENSIONS |
| Installation |
Flush mount |
| Front |
63 mm diameter |
| Front bezel |
69 x 69 mm (2.7 x 2.7 inch) |
| Body diameter |
52mm (2.0 inch) |
| Body depth |
31mm (1.2 inch) |
| INCLUDED ACCESSORIES |
| Shunt |
500 A / 50 mV |
| Cables |
10 meter 6 core UTP with RJ12 connectors |
| Temperature sensor |
n. a. |
|